Smarter Heating & Hot Water

Priority Domestic Hot Water (PDHW)

Dual flow temperatures on a cylinder system: hot, fast reheat, then cooler condensing heat for the radiators.

On a normal S Plan or Y Plan the boiler has one flow setpoint. That setpoint is almost always the cylinder’s — typically 65–75 °C — because the coil will not satisfy a 60 °C cylinder stat if the flow is cooler. Heating then runs at that same high temperature all winter, so a condensing boiler spends most of its life above the dew point. That is the problem PDHW is there to fix.

Priority domestic hot water is for a system or regular boiler and a stored cylinder. The cylinder call takes the full boiler output at a high flow. When the store is satisfied, heating returns at a lower weather-compensated or fixed flow. Output (kW) can also drop with the heating load, instead of sitting at the figure you needed for a combined coil-plus-radiator duty.

What it is not

A combi uses the same idea internally: a diverter throws the heat exchanger onto the plate when a tap opens, then back to heating. That is not what installers mean by PDHW. PDHW is stored hot water — open-vented regular or sealed system boiler — with a separate coil and a second temperature.

S Plan that can heat the cylinder and the radiators at once, on one boiler knob, is not PDHW either. Both 2-ports can be open; the boiler never learns there are two jobs.

Two-pipe, four-pipe, and X-Plan

There is more than one hydraulic way to get two temperatures. The software in the boiler is as important as the valves.

Y Plan mid-position sharing both ports at once is not priority. Convert it (W, S with cylinder lockout, four-pipe, or X-Plan) if you want dual temperatures.

Temperatures that actually work

Cylinder water: 60 °C at the stat (legionella). Primary flow to the coil: at least about 5 °C above that, or the cylinder never satisfies and the boiler sits on the programmer. Fast reheats use 70–80 °C for that window only.

Heating after the reheat: as low as the emitters allow. Weather compensation or a room sensor is the clean way. Fixed 45–55 °C is the usual retrofit if the radiators were not oversized. Building Regulations Part L now expects new heating systems to be designed around a 55 °C flow; PDHW is how you still get a hot cylinder without running 75 °C through the rads all day. Without dual setpoints see system / regular boiler flow temperature.

Coil rating is the recovery time. Undersized coil + large cylinder = a long priority period and a cooling house. If reheats regularly run past 20–30 minutes, check coil kW, pump, and primary sludge — not just the control wires.

What you gain

Heat pumps

A heat pump still runs a dedicated DHW cycle and pauses space heating. That is not gas PDHW. Flow is capped by the refrigerant; copy 80 °C boiler numbers onto it and you will not get them. Coil or plate area has to be for low-temperature heat.

What goes wrong

Gas work and unvented cylinder work stay with the correctly registered person. Use the manufacturer’s pipe and wiring sheet for the actual terminals — this page is the logic, not a substitute for the Intergas X-Plan leaflet or a Viessmann 4-pipe diagram.

Related