Worcester Bosch E9 Fault Code

E9, the reset button, and the fault indicator LED are flashing. Safety temperature circuit has tripped.

Fault codes / Worcester Bosch

E9 checks

StepCheckIf yesIf no / next
1Fully pumped sealed system?Go to step 3.Go to step 2.
2Open-vented: enough water in the F&E tank?Go to step 4.Top up, vent, reset for 3 seconds.
3Sealed system pressure between 1 and 2 bar?Go to step 4.Top up, vent, reset.
4Pump seized?Free the pump or replace it, refill/vent, reset.Go to step 5.
5Lead disconnected from flue and/or CH flow safety temperature limiter?Reconnect, reset.Continue limiter continuity checks, fuse SI 3, then PCB.

Gas work stays with a Gas Safe registered engineer. These steps are guidance from the manufacturer sequence, not a substitute for the handbook.