Enter analyser CO2 readings with the case open at maximum rate (H) and minimum rate (L). Pass/fail uses the original Hub Worcester Bosch FGA limits.
Max power, case open. Pass 8.5–10.1%
Min power, case open. Pass ≥ 7.5% and ≤ CO2 (H)
CO2 (H) PASS if 8.5% ≤ CO2 (H) ≤ 10.1%
CO2 (L) PASS if 7.5% ≤ CO2 (L) ≤ CO2 (H)