Enter analyser readings with the case open at maximum rate (H) and minimum rate (L). Pass/fail uses the original Hub Intergas FGA limits.
Max power, case open. Pass 3.85–5.6%
Max power, case open. Pass 8.6–9.6%
Min power, case open. Pass ≥ O2 (H) and ≤ 6.00%
Min power, case open. Pass ≥ 8.4% and ≤ CO2 (H)
O2 (H) PASS if 3.85% ≤ O2 (H) ≤ 5.6%
CO2 (H) PASS if 8.6% ≤ CO2 (H) ≤ 9.6%
O2 (L) PASS if O2 (H) ≤ O2 (L) ≤ 6.00%