Vaillant F83 Fault Code

Flow and/or return NTC temperature-change fault

Back to Vaillant Fault Codes

Gas Safe: Gas work, flue work, and PCB replacement on a gas boiler must be carried out by a Gas Safe registered engineer. Homeowners can check obvious items such as heating pressure, condensate overflow, and whether a control is unplugged — then call an engineer.

Always confirm the part number against the boiler GC number and the installation manual before ordering.

Overview

F.83: at burner start the flow and/or return NTC did not see a temperature rise (or the rise was too small). Usually not enough water, air, or an NTC not actually on the pipe — not a random electronics code.

Vaillant meaning: Flow and/or return NTC temperature-change fault

Possible causes

Possible solutions

  1. Check cold pressure (about 1.0–1.5 bar) and bleed the boiler / high points. See boiler pressure and F.22.
  2. Confirm both NTCs are tight on flow and return.
  3. Prove the pump runs when a heat demand starts (F.23 / F.24 / F.75 overlap).
  4. Replace an NTC only if mounting is correct and that sensor never moves in diagnostics (D.40 / D.41).

Possible parts needed

Vaillant NTC SensorVaillant Flow / Return NTC 193592
Vaillant PCB X20 Connector
Vaillant PCB X20 connector (typical NTC loom)