Remeha Fault Codes

Display codes for Remeha boilers.

Back to fault codes

Fault CodeDescriptionPossible CauseCheck / SolutionModels
E0Flow or return sen- sor fault.Short circuit in the flow, return or boiler temperature sensor.
Defective or not (properly) con- nected flow, return or boiler temperature sensor.
Short circuit in the flow, return or boiler temperature sensor.
Check the wiring and the connections of the sensors visually: are the plugs all correctly in position? With a multimeter: measure the resistance in the wir- ing and connection.
Check that the sensors are working; take the sensors out * and measure the resistance with a multimeter at room temperature (20 - 25å¡C); the sensor is working properly if the resistance is between 12 and 15 kë©.
Avanta
E1Flow temperature is higher than the set maximum tem- peratureInsufficient water.
No through flow.
Too much air in the system.
Deviation in the flow or return temperature sensor.
Check the minimum water pressure, read off the gauge.
Check that the pump is working; turn the spindle with a screwdriver, if that works but the pump still does not respond, check the wiring; if that is in order the pump is faulty.
Vent the system.
Check that the sensors are working; take the sensors out * and measure the resistance with a multimeter at room temperature (20 - 25å¡C); the sensor is working properly if the resistance is between 12 and 15 kë©.
Avanta
E2Return temperature is higher than the flow temperatureInsufficient water.
No through flow.
Too much air in the system.
Sensors not wired correctly
Deviation in the flow or return temperature sensor.
Check the minimum water pressure, read off the gauge.
Check that the pump is working; turn the spindle with a screwdriver, if that works but the pump still does not respond, check the wiring; that is in order the pump is faulty.
Vent the system.
Check the wiring between sensors and control unit.
Check that the sensors are working; take the sensors out * and measure the resistance with a multimeter at room temperature (20 - 25å¡C); the sensor is working properly if the resistance is between 12 and 15 kë©.
Avanta
E3Control unit or earth faultMains supply not correctly earthed.
Control unit faulty.
Check that the power supply from the switch spur is properly earthed, if that is the case the control unit is faulty.Avanta
E4More than 5 start attempts without any flame forma- tion.No ignition spark.
A spark but no flame.
There is a flame but no, or insufficient ionisation (lower than 3 or higher than 9 ë_A)
Check:
the connection between the ignition wire and the ignition trafo;
the ignition wire and electrode for ÌÓdielectric breakdownÌ¥;
the inter-electrode distance, this should be 3-4 mm; that
the ignition electrode is properly earthed.
Check:
‰Û¢ the connection between the ignition wire and the ignition trafo;
‰Û¢ the ignition wire and electrode for ‰Û÷dielectric breakdown‰Ûª;
‰Û¢ the inter-electrode distance, this should be 3-4 mm; that
the ignition electrode is properly earthed.
Check that:
‰Û¢ the gas tap is open;
‰Û¢ the gas pre-pressure is sufficient;
‰Û¢ the gas pipe is de-aerated;
‰Û¢ the gas valve is energised during ignition and opens;
‰Û¢ the electrode is correctly fitted and clean;
‰Û¢ the CO2 adjustment at low and full load;
‰Û¢ there is no obstruction / fitting fault in the gas pipe;
‰Û¢ there is no obstruction in the air supply or flue (e.g. a
blocked siphon); there is no recirculation of flue gasses (either inside or outside the boiler).
Check:
‰Û¢ the flame, is the heart of the flame visible and the flame stable?
‰Û¢ the CO2 adjustment at low and full load;
‰Û¢ that the ignition electrode is correctly earthed;
‰Û¢ visual check of the ignition/ionisation electrode: look for white oxide film
(remove with sandpaper or a screwdriver); look at the shape (are the pins still the original shape and is the distance between the two ends of the pins between 3 and 4 mm).
Avanta
E5No ionisation or ionisation failure more than 5 times during one heat demand.CO2 wrongly adjustedCheck:
‰Û¢ CO2 adjustment on the gas block;
‰Û¢ ignition/ionisationpin;
‰Û¢ flue/air-supplyconnections;
‰Û¢ gas flow at full load;
‰Û¢ if there is no recirculation of flue gasses (either inside or outside the boiler).
Avanta
E6Unwanted flame formationFaulty control unit, replace control unit.Avanta
E7No water in the boiler or the pump is not workingInsufficient water.
No through flow.
Too much air in the system.
Wrong pump wiring.
Check the minimum water pressure, read off the gauge and check for leaks.
Check that the pump is working; turn the spindle with a screwdriver, if that works but the pump still does not respond, check the wiring; that is in order the pump is faulty.
Vent the system.
Check wiring from and to control unit.
Avanta
E8Fan faultFan is not working
Fan does not stop
Check:
‰Û¢ fanfunction;
‰Û¢ fan wiring and connection.
Check:
‰Û¢ fanfunction;
‰Û¢ fan wiring and connection;
‰Û¢ excess chimney draught.
Avanta
E10No through flow during venting cycleInsufficient water.
No through flow
Too much air in the system.
Wrong pump wiring.
Check the minimum water pressure, read off the gauge and check for leaks.
Check that the pump is working; turn the spindle with a screwdriver, if that works but the pump still does not respond, check the wiring; that is in order the pump is faulty.
Vent the system.
Check wiring from and to control unit.
Avanta
E11Air box tempera- ture to highAir leakage from heat exchang- er to air boxCheck:
‰Û¢ The sealing of the viewing glass;
‰Û¢ Whether front plate of heat exchanger is properly tightened
‰Û¢ Front plate sealing;
‰Û¢ Whether ignition electrode is properly fitted
Avanta
E13Heat-exchanger fuse protection has responded; replace the heat exchanger after finding and solving the cause.Heat exchanger faulty.
Insufficient water.
No through flow.
Check wiring between heat exchanger fuse.
Check the minimum water pressure, read off the gauge and check for leaks.
Check that the pump is working; turn the spindle with a screwdriver, if that works but the pump still does not respond, check the wiring; that is in order the pump is faulty.
Avanta
E43Parameter limitsAutomation settingsReplace d f / d U settings, see Par. 2.9.10
If this error code still returns after resetting; please contact Broag.
Avanta
E44Parameter checkAutomation settingsReplace d f / d U settings, see Par. 2.9.10
If this error code still returns after resetting; please contact Broag.
Avanta
E45Default parametersAutomation settingsReplace boiler control unit.Avanta

Gas work stays with a Gas Safe registered engineer. Some codes only apply to a named range — check the model column.