Heating expansion vessel calculator

System volume, static height, flow temperature and PRV. Fit size is CIBSE Table 5.15, checked against Zilmet / EN 12828.

System volume

Estimate is a trade allowance, not measured content

Domestic or commercial. Up to 20,000 L.

Typical boiler 3.0. Must stay above cold fill.

80 °C
5 m · 0.50 bar

Vessel to highest pipe, 0.1 bar per metre. Pre-charge is set from this, not left at the usual 0.75 bar factory charge.

Fit this vessel
12 L
Next stock size from CIBSE Table 5.15
0.50 bar
Factory is usually 0.75 bar — drop to this, system empty
CIBSE minimum
8.3 L
Before rounding up
Cold fill
1.00 bar
Static + 0.5 bar once the system is full
Zilmet / EN 12828
4.6 L
Water only, no glycol
System 100 L e 0.0287 CIBSE k 0.0833 Acceptance 63%

Method

Static pressure = height (m) ÷ 10 (0.1 bar per metre). Set the vessel pre-charge to that pressure, not below 0.5 bar, on the Schrader with the system empty. New vessels are usually factory-charged to 0.75 bar (right only for about 7.5 m of static head).
Cold fill = static + 0.5 bar (BS EN 12828 water reserve when cold).
Vessel volume for fitting is from CIBSE Domestic Heating Design Guide Table 5.15: system litres × multiplying factor for the safety-valve setting and vessel charge / initial pressure. Example: 100 L, 3.0 bar valve, 0.5 bar charge → 8.3 L, so fit 12 L.
Below 80 °C the Table 5.15 result is scaled by e(T) / e(80 °C), because the CIBSE table is for conventional boiler temperatures. Heat-pump flow of 45 °C expands much less water.
e is the volume change of water from 10 °C to the flow temperature you set.
Acceptance = 1 − (p₀ + 1) / (PRV + 1). The Zilmet check is V = e × Vs / acceptance (EN 12828 / VDI 4708, water only). Same example: about 4.6 L, stock 8 L. CIBSE is what we size to. Stock vessels 8–900 L. Glycol needs a larger vessel.

CIBSE Table 5.15 is for sealed heating systems at conventional temperatures. Open-vented systems do not use this calculation. Cold fill must stay below the PRV. Sealed-system charging must be done by a suitably qualified person.