Baxi EcoBlue Heat Only Fault Codes

LED flash codes for EcoBlue heat-only. Recovered from the original hub.myboiler.com table.

Fault codes / Baxi

Error codePossible faultInstaller action
FLASHED Green 1 TIMEBoiler temp reached
3 GREEN FLASHESTemporary Flame Loss (No Reset Required)Temporary error, self-reset. If it continues it goes to 3 red flashes (lockout).
4 GREEN FLASHESCommunication Fault Between PCB And ControlTemporary error, self-reset.
5 GREEN FLASHESParameter Error On PSU/PCBTemporary error, self-reset.
6 GREEN FLASHESMiscellaneous ErrorTemporary error, self-reset.
ONE RED FLASHSensor Error: Sensor Fault, Temperature Fault Or Flow FaultCheck wiring; sensors about 12 kΩ at 25 °C; sensor in the pocket; AAV open; system full and vented; pump running; flow/return orientation; blockages.
2 RED FLASHESBoiler Overheat TrippedVent the system; check water pressure; continuity across the overheat stat and APS if fitted; circulation direction, pump, valves; wiring; not air-locked.
3 RED FLASHESIgnition Fault. Boiler Has Failed To Light After 5 AttemptsCheck wiring, supply pressure, purge air, spark, electrode condition, gas valve opening, condensate drain.
4 RED FLASHESFan FaultIf the fan is not running, check power to the gas-air unit. If it is running, check APS (if fitted). Check the flue for blockages.
5 RED FLASHESParameter Or PSU ErrorCheck PCB and loom; replace PSU and recommission; check wiring.
FLASHES RED 6 TIMESMiscellaneousCheck wiring connections. If needed replace the PU and/or control/fan assembly.

Gas work stays with a Gas Safe registered engineer. These steps are guidance from the manufacturer sequence, not a substitute for the handbook.