Baxi Duo-tec, Platinum & Megaflo Fault Codes

Range-specific Baxi display codes. Recovered from the original hub.myboiler.com table.

Fault codes / Baxi

Error codePossible faultInstaller action
E10Outdoor Sensor ErrorOutdoor sensor fault. Check the sensor and that the IP menu outdoor-sensor value reads correctly.
E20Central Heating Thermistor Sensor FaultCheck resistance across the sensor is about 12 kΩ at 25 °C. If not, suspect the sensor.
E28Flue Thermistor FaultCheck the flue sensor value. Check for a blocked flue.
E110Boiler Overheat TrippedCheck boiler temperature is not over 110 °C; continuity across the overheat stat; pump circulation; clear air from the system.
E119System Pressure Low (< 0.5 Bar)Check for leaks; check expansion-vessel charge; add water via the filling loop. Restoring pressure resets the error.
E125Primary Water Circulation FaultCheck the pump; system full of water; clear air; check for blockages; check thermistors are located correctly.
E131Flue Overheat LockoutMay follow a power cut — try reset. Flue NTC exceeded 130 °C; check resistance. Possible blocked heat-exchanger waterways.
E133Ignition FaultCheck wiring, supply pressure, purge air, spark at electrode, electrode condition, gas valve opening, condensate drain.
E160Fan FaultCheck the fan and cable. Probable fan failure.
E161Fan FaultCheck the fan and cable. Probable fan failure.
E164Heating Flow Switch Error (Ireland) / Pressure Sensor Error (UK)HEa Irish system boilers have flow switches — check switch operation. UK boilers: fit the correct PCB.
E167PCB Fault
E168PCB Lock OutMay follow a power-supply problem. Try reset.
E193Circulation FaultIf it persists, E125 usually follows.