Calculate radiator output at different delta T values for heat pump systems and conventional heating.
Emitter Output at Delta T
Emitter Output (BTU / KW)
Select Delta T (°C / K)
Emitter Output (at Delta T)
1000.00
BTU / KW
This calculator will tell you what output you will end up with if you reduce the delta T to the selected from the dropdown.
Required Radiator Output at Delta 50°C
Heatloss (BTU / KW required)
Select Delta T (°C / K)
Output of Emitter at Delta 50°C needed
1000.00
BTU / KW
This calculator is used to work out which standard radiators at 50 degrees delta to meet the needs of heat pumps.
Delta T Conversion Factor Table
Delta T (°C / K)
Conversion Factor
5
0.05
10
0.123
15
0.209
17.50
0.257
20
0.304
25
0.406
30
0.515
35
0.629
40
0.748
45
0.872
50
1.000
55
1.132
60
1.267
65
1.406
70
1.694
Important: These calculations are based on radiator performance curves. Always consult manufacturer data sheets for specific radiator models and verify calculations with a qualified heating engineer.